Input and Operating Parameters
Input Connection: Designed as 3+1 PHASE (Three phase and neutral).
Operational Continuity: Suitable for continuous 24/7 operation at full load (0% - 105%).
Maximum Input Voltage Range: The maximum voltage that can be applied to the input is between 0V and 450V (Phase-Neutral).
Regulator Operating Range: The regulator maintains stable operation within the 65V to 290V (Phase-Neutral) range.
Protection Voltage: It automatically enters protection mode if the voltage drops below 45V or exceeds 300V (Phase-Neutral).
Correction Range: It performs voltage regulation efficiently between 90V and 290V (50 Hz).
Operating Frequency: The frequency range is from 47Hz to 63Hz.
Correction Speed: Features high speeds, such as approximately 2 ms for frequency changes and approximately 16-60 ms for step changes.
Switching Technology: Utilizes a Thyristor Controlled (Static Regulator) system, offering high speed and reliability.
Environmental and Structural Conditions
Operating Temperature: Resistant to extreme temperature conditions; operates between -40°C and +55°C.
Relative Humidity: Less than 96% in non-condensing environments.
Operating Altitude: Can operate smoothly up to 3,000 meters below sea level.
Protection Class: Has an IP21 protection rating.
LCD Display and Advanced Monitoring System
Display Count: The device has 3 LCD displays, which can operate between -40°C and +55°C.
Basic Information Displayed: The screens instantly show Input Voltage, Output Load Percentage, Regulator Status, and Error Information.
Warnings and Error Messages: Also includes critical warnings for Overload, Overheat, Input/Output Faults, countdown time, and multi-display functionality.
Menu Control: All parameters can be adjusted and access to detailed information pages is provided via the Menu Button.
Details Tracked via Menu: The menu allows tracking of Software Version, Static Step Count, Warranty Number, Total Operating Hours, and the Maximum/Minimum Voltage/Current values since the last start.
Minimum Mean Time Between Failures (MTBF): Determined as 61,320 hours.
Error Logging: Errors are tracked using circular logic (FIFO) for 65,535 events over a period of 7 years. All error causes are permanently stored in a 1024 bit EEPROM memory.